Name | Float switch |
---|---|
Type | TM S-60 – ref: 2504-2-…E |
Density of the product | 0,75 Kg/l |
Maximum pressure | +1 bar |
Switching voltage | 24 – 250 V AC/DC |
Power consumption | 60 VA in AC; 60 W in DC |
Contact function | 1 NO + 1 NC |
Capacity of the contact | 1 mA – 1 A (for resistive loads) For inductive or capacitive loads, reduce at 50% |
Ambient temperature | +0° C – +150º C |
Protection | IP6X according to DIN EN60529 |
Float weight | 0,22 Kg |
Cable length | 05 – 5 m cable – ref: 2504-2-05E 10 – 10 m cable – ref: 2504-2-10E 20 – 20 m cable – ref: 2504-2-20E |
Materials: | |
Float | PTFE |
Cable | Double isolation PTFE |
Counterweight | PTFE |
- Productos
- Control of liquids
- TM S-60
Intended use
The floats are to be used to control the level in the filling and emptying processes of tanks, wells and containers in which aggressive liquids, like acids, alkaloids and a wide range of chemical products or hydrocarbons are used.
Function
When the level of the liquid reaches the level of the float switch, the float changes its position an angle and the Reed contact open or close the electric circuit due to this deviation.
It is necessary to install 2 devices to control of the maximum and the minimum levels automatically.
Mechanical connection
It is simple: the switch literally hangs on its own cable at the desired height and is fixed to the ceiling or to one side of the tank adjusting the distance of the counterweight, if it was requested.