The floats are to be used to control the level in the filling and emptying processes of tanks, wells and containers in which aggressive liquids, like acids, alkaloids and a wide range of chemical products or hydrocarbons are used.

When the level of the liquid reaches the level of the float switch, the float changes its position an angle, the ball inside its deviated and activates a micro switch due to this deviation.

It is necessary to install 2 devices to control of the maximum and the minimum levels automatically.

It is simple: the switch literally hangs on its own cable at the desired height and is fixed to the ceiling or to one side of the tank.

Dimensions

Approximate measures given in mm.

Technical data

NameFloat switch
TypeTMHY-E – ref: 2504-1-…E
Density of the product0,80 Kg/l – 1,10 Kg/l
Maximum pressure+4 bar
Switching voltage250 V AC
Switching function1 NO + 1 NC
Capacity of the contact16 A / 250 V AC (for resistive loads)
For inductive or capacitive loads, reduce at 50%
Ambient temperature-40° C – +90° C depending on the liquid to control
ProtectionIP68 according to DIN EN60529
Float weight0,30 Kg
Counterweight weight0,25 Kg
Cable length05 – 5 m cable – ref: 2504-1-05E
10 – 10 m cable – ref: 2504-1-10E
15 – 15 m cable – ref: 2504-1-15E
Materials:
FloatPolypropylene copolymer,
Hypalon press-vulcanised
CableDouble isolation Hypalon
CounterweightResin

Explore all our level controls

Need more information?