The floats are to be used to control the level in the filling and emptying processes of tanks, wells and containers in which scaling non-clean or residual waters are used, with or without foam in its surface.

When the level of the liquid reaches the level of the float switch, the float changes its position an angle, the counterweight inside its deviated and activates a micro switch due to this deviation.

When the level of the liquid overreaches the level of the float switch, the float remains in its position in the water due to the counterweight, makes a strenght to the cable that allow the installation of more floats without rolling their cables and reduces the waste’s adhesion.

It is necessary to install 2 devices to control of the maximum and the minimum levels automatically.

It is simple: the switch literally hangs on its own cable at the desired height and is fixed to the ceiling or to one side of the tank.

Dimensions

Approximate measures given in mm.

Technical data

NameFloat switch
TypeTM-E — ref: 2504-0-…E
Density of the product0,95 Kg/l – 1,10 Kg/l
Maximum pressure+3 bar
Switching voltage250 V AC
Switching function1 NO + 1 NC
Capacity of the contact10 A / 250 V AC (for resistive loads)
For inductive or capacitive loads, reduce at 50%
Ambient temperature+0° C – +60° C
ProtectionIP68 according to DIN EN60529
Float weight0,79 Kg
Cable length06 – 6 m cable – ref: 2504-E
10 – 10 m cable – ref: 2504-0-10E
15 – 15 m cable – ref: 2504-0-15E
20 – 20 m cable – ref: 2504-0-20E
30 – 30 m cable – ref: 2504-0-30E
Materials:
FloatPolypropylene
CableDouble isolation PVC
Compression glandEPDM

Explore all our level controls